Failure of In-Service Stainless-Steel Chemical Storage Tanks Fasteners and Gaskets – A Case Study

Wafra Joint Operations is in the west central part of the Kuwait-Saudi Arabia Neutral Zone. The oilfield produces light and heavy oil and exports it to its various customers after processing. Upstream field consists of various Sub Centres where crude, oil and water being separated, and the separated crude transported to the main gathering centre for further processing in two different trains. The produced water being disposed/injected via water disposal and injection facilities after treatment.

Product Number: 51323-18790-SG
Author: Hamad Salem Al-Ajmi, A/Rahman Al-Ghamdi, Tariq Kamshad, Yousef Bahbahani, Salem Al-Qahtani, Manickavasagan Sabesan, Bakheet Al-Yami
Publication Date: 2023
$0.00
$20.00
$20.00

This paper demonstrates a case study associated with the improper installation of non-stainless-steel materials in chemical tanks against design specification, which explicitly called for the use of stainless-steel fasteners and gaskets. An operating facility required the substitution of current chemicals with new ones, and as part of the management of change (MOC) process, the cleaning and inspection of the tanks was required. Internal visual inspection (IVI) of the tanks revealed severe corrosion of the tank internal fasteners, including fasteners supporting structural elements of the tank central periphery. Positive Material Identification (PMI) testing was conducted and concluded that chrome-manganese bolt nuts were used during construction stage which does not match with the design recommended material, which is stainless steel AISI Type 316, ASTM A 193 GR. B7 and ASTM A 194 GR. 8M. The causal factors for the fastener’s corrosion were determined to arise from galvanic corrosion from using dissimilar materials alongside very corrosive environment. Similarly, it was observed that all tanks manway suffered from localized and crevice corrosion due to the use of non-asbestos gaskets instead of spiral wound metallic stainless steel AISI 316 gaskets as per design. Consequently, chemical incompatibility of the gasket led to flange surface crevice and localized corrosion.

This paper demonstrates a case study associated with the improper installation of non-stainless-steel materials in chemical tanks against design specification, which explicitly called for the use of stainless-steel fasteners and gaskets. An operating facility required the substitution of current chemicals with new ones, and as part of the management of change (MOC) process, the cleaning and inspection of the tanks was required. Internal visual inspection (IVI) of the tanks revealed severe corrosion of the tank internal fasteners, including fasteners supporting structural elements of the tank central periphery. Positive Material Identification (PMI) testing was conducted and concluded that chrome-manganese bolt nuts were used during construction stage which does not match with the design recommended material, which is stainless steel AISI Type 316, ASTM A 193 GR. B7 and ASTM A 194 GR. 8M. The causal factors for the fastener’s corrosion were determined to arise from galvanic corrosion from using dissimilar materials alongside very corrosive environment. Similarly, it was observed that all tanks manway suffered from localized and crevice corrosion due to the use of non-asbestos gaskets instead of spiral wound metallic stainless steel AISI 316 gaskets as per design. Consequently, chemical incompatibility of the gasket led to flange surface crevice and localized corrosion.

Also Purchased
Picture for 02421 Film Rupture and Repassivation on...
Available for download

02421 Film Rupture and Repassivation on Straining Stainless Steel Electrodes

Product Number: 51300-02421-SG
ISBN: 02421 2002 CP
Author: D. A. Jones, V. S. Raja, L. G. McMillion, and K. S. Raja
$20.00
Picture for 02115 CATHODIC PROTECTION OF UNDERGROUND...
Available for download

02115 CATHODIC PROTECTION OF UNDERGROUND STORAGE TANK SYSTEMS WITH DIRECTIONALLY DRILLED GROUNDBEDS BELOW THE TANKS

Product Number: 51300-02115-SG
ISBN: 02115 2002 CP
Author: Mark Cadle and Tim Whited
$20.00
Picture for 01591 Application Of The 100mv Polarization
Available for download

01591 Application Of The 100mv Polarization Criteria For Aboveground Storage Tank Bottoms

Product Number: 51300-01591-SG
ISBN: 01591 2001 CP
Author: Louis Koszewski
$20.00