10217 Corrosion of Fire Protection System Lines at the Nevada Test Site's Device Assembly Facility

Product Number: 51300-10217-SG
ISBN: 10217 2010 CP
Author: Glenn Edgemon, Dr. Graham Bell and Gary G. Baker
Publication Date: 2010
$0.00
$20.00
$20.00
The Device Assembly Facility (DAF) is a collection of 30 individual steel-reinforced buildings connected by a rectangular racetrack corridor built in the Nevada desert in the mid-1980s. The DAF fire suppression system includes 29 carbon steel lead-in lines that run underground from the header loop line to a variety of risers inside the DAF. The lead-in lines are fabricated from 4-in. or 6-in. diameter carbon steel pipes lined and coated with coal tar enamel (CTE). Particles and flakes of the CTE lining have been appearing in water used to flush the fire suppression piping since the installation of the system. Discussions with DAF personnel indicate that the carbon steel lines were not flangefitted together (as designed) during installation at the DAF; instead, the sticks of pipe used to form the lead-in lines were welded together. The welding caused substantial damage to the interior CTE lining. Screens have since been installed in the lead-in lines to prevent CTE particles and flakes from clogging sprinkler heads should their use be required in an emergency. An integrity assessment was recently performed to determine the nature and extent of corrosion damage and to determine the mechanism responsible for the delamination of the CTE lining. Borescopic video and Remote Field Tool (RFT) inspections confirmed that the CTE lining was substantially damaged by welding operations during construction of the lead-in line system. Several forms of corrosion are active or likely active in the system including general corrosion, MIC, pitting, crevice corrosion, and galvanic cell corrosion. No sessile samples were collected, but tubercle-like growths were observed and water testing confirmed that MIC-inducing bacteria are present in all the lead-in lines br>
Keywords: microbiologically induced corrosion, pipeline corrosion, coat tar enamel, Device Assembly Facility, fire suppression system
The Device Assembly Facility (DAF) is a collection of 30 individual steel-reinforced buildings connected by a rectangular racetrack corridor built in the Nevada desert in the mid-1980s. The DAF fire suppression system includes 29 carbon steel lead-in lines that run underground from the header loop line to a variety of risers inside the DAF. The lead-in lines are fabricated from 4-in. or 6-in. diameter carbon steel pipes lined and coated with coal tar enamel (CTE). Particles and flakes of the CTE lining have been appearing in water used to flush the fire suppression piping since the installation of the system. Discussions with DAF personnel indicate that the carbon steel lines were not flangefitted together (as designed) during installation at the DAF; instead, the sticks of pipe used to form the lead-in lines were welded together. The welding caused substantial damage to the interior CTE lining. Screens have since been installed in the lead-in lines to prevent CTE particles and flakes from clogging sprinkler heads should their use be required in an emergency. An integrity assessment was recently performed to determine the nature and extent of corrosion damage and to determine the mechanism responsible for the delamination of the CTE lining. Borescopic video and Remote Field Tool (RFT) inspections confirmed that the CTE lining was substantially damaged by welding operations during construction of the lead-in line system. Several forms of corrosion are active or likely active in the system including general corrosion, MIC, pitting, crevice corrosion, and galvanic cell corrosion. No sessile samples were collected, but tubercle-like growths were observed and water testing confirmed that MIC-inducing bacteria are present in all the lead-in lines br>
Keywords: microbiologically induced corrosion, pipeline corrosion, coat tar enamel, Device Assembly Facility, fire suppression system
Product tags
Also Purchased
Picture for 00653 REMEDIATION OF CORROSION PROBLEMS
Available for download

00653 REMEDIATION OF CORROSION PROBLEMS INSIDE FIRE SPRINKLER SYSTEM PIPING

Product Number: 51300-00653-SG
ISBN: 00653 2000 CP
Author: S. Steven Carl
$20.00
Picture for 04602 A Microbiologically Influenced Corrosion
Available for download

04602 A Microbiologically Influenced Corrosion Study in Fire Protection Systems

Product Number: 51300-04602-SG
ISBN: 04602 2004 CP
Author: Geary G. Yee and Michael R. Whitbeck, FM Global Research
$20.00
Picture for 00401 MICROBIOLOGICALLY INFLUENCED CORROSION
Available for download

00401 MICROBIOLOGICALLY INFLUENCED CORROSION IN FIRE PROTECTION SPRINKLER SYSTEMS

Product Number: 51300-00401-SG
ISBN: 00401 2000 CP
Author: Daniel H. Pope and Rebecca M. Pope
$20.00